Analysis of Zero-Value and Broken-String Faults in Porcelain Insulators
Aug 05, 2026
Leave a message
Mechanism of Porcelain Insulator String Breakage
For porcelain insulators, defects such as micro-cracks in the insulator head allow moisture ingress during operation, reducing the insulation resistance of the head (resulting in a "zero-value insulator"). When the insulator string experiences a flashover-caused by a lightning strike or other factors-the discharge path through the insulator head carries the majority of the energy. This occurs because the resistance at the head is extremely low compared to the relatively high resistance along the discharge path across the insulator sheds. The heat generated by the arc passing through the insulator head causes the insulator to shatter, leading to the breakage of the insulator string.
Thus, the development of a zero-value defect is the critical factor leading to porcelain insulator string breakage.
Causes of Zero-Value Defects
① Poor Insulator Quality
Defects in the manufacturing process of the cemented interface or the quality of the porcelain material itself can lead to the formation of zero-value insulators.
The cemented interface of a porcelain insulator involves materials with differing coefficients of thermal expansion-specifically porcelain, cement, and steel. A buffer layer (typically made of asphalt or similar material) is usually applied; if this layer is too thin or fails to interface properly with the porcelain and cement, external temperature fluctuations can cause the interface to crack.
Sand holes or excessively large grain sizes within the porcelain body can lead to the formation of internal micro-cracks during long-term operation. As these cracks propagate, they eventually result in the insulator becoming a zero-value unit.
② Repeated Lightning Strikes
When a tower is struck by lightning, the insulator may be subjected to impulse voltages characterized by both steep wavefronts and high amplitudes. Under these conditions, the porcelain head-where voltage stress is highest and insulation is relatively weaker-may sustain damage from partial discharge. Repeated exposure to steep-fronted impulse waves causes this damage at the porcelain head to progressively worsen, eventually leading to the formation of a zero-value insulator.③ Excessive mechanical load
Severe ice accretion or high winds exceeding design speeds can subject insulators to excessive mechanical stress; this may cause cracking at the location of the insulator's steel pin, resulting in "zero-value" insulators (insulators that have lost their insulating capability).
In the past, zero-value porcelain insulators were primarily caused by material defects; while advancements in manufacturing technology have reduced the incidence of such defects, the issue of zero-value insulators resulting from repeated lightning strikes over long service lives now requires greater attention.
Countermeasures
① Strengthen zero-value detection
Zero-value detection involves a heavy workload, and detection efficiency is closely linked to the method used; performing live measurements on towers is difficult, making this a challenge that has yet to be fully resolved. With current technology, the following measures can be adopted to improve detection efficiency:
A Conduct spot checks on porcelain insulators in lightning-prone areas: remove a sample of insulators for laboratory testing; perform insulation resistance tests under high-humidity conditions (as some low-value insulators are difficult to detect when dry); and conduct steep-front impulse tests to check for damage to the insulator head;
B Increase the test voltage for insulation resistance measurements;
② Adopt lightning diversion measures
Implement lightning diversion measures-such as parallel gaps or surge arresters-to divert lightning current away from the insulators, thereby reducing the probability of insulator damage.
③ Improve the line's lightning withstand capability
Upgrade grounding systems and enhance insulation levels to minimize the amplitude of impulse voltage experienced by insulators following a lightning strike.